TM024 Premier Loline Solar Drain back Service Instructions REV: A
D.O.I: 12/12/2007
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
36
Fault Finding Chart 1.8
Clean the collector glass or
replace the collector.
Is the
collector glass
broken or
dirty?
YES
Is the
coating on the
collector absorber plate
deteriorating?
Replace the collector.
NO
YES
NO
1.8
Is the
daily water
usage exceeding the
solar heating
capacity?
Is
usage time
not suitable to hours
when solar gain is the greatest?
i.e. morning usage with
west facing
collectors
YES
Reposition collectors to northerly
aspect or advise customer that
boosting will be required more often.
YES
Is
the problem
only evident during
winter?
NO
Advise customer that boosting will be
required more often during the winter
months.
YES
Advise customer on a usage
pattern that will suit needs.
NO
Solar system operational.
Suggest a usage pattern that
will minimise depletion of
hot water at night.
NO
Is the
daily water
usage exceeding the
solar heating
capacity?
Suggest a usage pattern that
will minimise depletion of
hot water at night.
NO
What was
the original
complaint
for?
Refer to heater
exploded view
No hot water
Insufficient hot water
or high energy bills
YES
Are
the solar hot &
cold pipes
insulated?
YES
Solar hot and cold pipes must be
insulated. Uninsulated pipe work will
result in inefficient operation and
high (booster) energy bills.
NO
Is the
dip tube fitted
and in the correct
position?
Replace or reposition dip tube
correctly.
YES
NO