Model RSNM- Series A042CK A042JK A048CK A048JK
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 43,000 [12.6] 43,000 [12.6] 48,000 [14.06] 48,000 [14.06]
EER/SEER
2
11.1/13 11.1/13 11.3/13 11.3/13
Nominal CFM/AHRI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661] 1600/1550 [755/731] 1600/1550 [755/731]
AHRI Net Cooling Capacity Btu [kW] 41,500 [12.16] 41,500 [12.16] 46,000 [13.48] 46,000 [13.48]
Net Sensible Capacity Btu [kW] 31,500 [9.23] 31,500 [9.23] 35,500 [10.4] 35,500 [10.4]
Net System Power kW 3.74 3.74 4.07 4.07
Net Weight lbs. [kg] 333 [151] 333 [151] 349 [158] 349 [158]
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
3
76 76 78 78
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 12.65 [1.18] 12.65 [1.18] 16.54 [1.54] 16.54 [1.54]
Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Net Latent Capacity Btu [kW] 10,000 [2.93] 10,000 [2.93] 10,500 [3.08] 10,500 [3.08]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.78 [0.54] 5.78 [0.54] 5.78 [0.54] 5.78 [0.54]
Rows / FPI [FPcm] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5] 3 / 13 [5]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm]
4
1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 3400 [1604] 3400 [1604] 4200 [1982] 4200 [1982]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 875 875 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/11x9 [279.4x228.6] 1/11x9 [279.4x228.6] 1/11x9 [279.4x228.6] 1/11x9 [279.4x228.6]
Drive Type/No. Speeds Direct/2 Direct/2 Direct/2 Direct/2
No. Motors 1 1 1 1
Motor HP 1/2 1/2 3/4 3/4
Motor RPM (Nominal) 1075 1075 1075 1075
Motor Frame Size 48 48 48 48
Filter—Type Field Supplied Field Supplied Field Supplied Field Supplied
Furnished No No No No
(No.) Size Recommended in. [mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] (R-410A) 86 [2438] 86 [2438] 114 [3232] 114 [3232]
Weights
Ship Weight lbs. [kg] 357 [162] 357 [162] 375 [170] 375 [170]
CONTINUED
NOMINAL SIZES 2-5 TONS [7-17.6 kW]
[ ] Designates Metric Conversions
9
GENERAL DATA—RSNM- SERIES
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are
suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
4. Standard 3/4" PVC P-Trap provided.