92-24161-38-01SUPERSEDES 92-24161-38-00INSTALLATION INSTRUCTIONSFOR UPFLOW/HORIZONTAL INDUCED DRAFT GASFURNACES(-)GPN/(-)GPP SERIES

Seite 2 - INSTALLATION CHECKLIST

10Combustion air must be free of acidforming chemicals; such as sulphur,fluorine and chlorine. These elementsare found in aerosol sprays,detergents, b

Seite 3 - CONTENTS

11a. One square inch for each 3000BTUH of the total input rating of allequipment located in the enclosure,ANDb. Not less than the sum of the areasof a

Seite 4 - SAFETY INFORMATION

12FIGURE 7OUTSIDE AIR USING A HORIZONTAL INLET & OUTLETFIGURE 8COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULLB: Method 3For the optim

Seite 5 - GENERAL INFORMATION

13GENERAL INFORMATIONThe furnace must be vented inaccordance with these instructions,National Fuel Gas Code, ANSI Z223.1and/or the Natural Gas Install

Seite 6 - UPFLOW/HORIZONTAL MODELS

14“B-1” VERTICAL VENTINGType “B-1” vents must be installed inaccordance with the terms of theirlistings and the vent manufacturer’sinstructions.“B-1”

Seite 7 - SITE SELECTION

15EXISTING VENT SYSTEMSIMPORTANT RETROFITVENTING INSTRUCTIONSIf this furnace is a replacementinstallation, ALWAYS INSPECT theexisting vent system to b

Seite 8 - HORIZONTAL UNITS

16FIGURE 12GAS PIPING INSTALLATIONGAS PIPE INSTALLATIONGAS SUPPLY AND PIPINGGAS SUPPLY THIS FURNACE IS EQUIPPED ATTHE FACTORY FOR USE ONNATURAL GAS ON

Seite 9 - REQUIREMENTS

TABLE 3TABLE 4NATURAL GAS ORIFICE DRILL SIZE (4% PER 1000 FT. DE-RATE)BURNER INPUT (PER BURNER) 25,000 BTU @ SEA LEVEL17GAS PRESSUREIMPORTANT: The max

Seite 10 - AIR FROM ATTIC/CRAWL SPACE

18TABLE 6LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)SETTING GAS PRESSUREThe maximum gas supply pressure tothe furnace should be 10.5” w.c.natural gas, or

Seite 11

19TABLE 8TABLE 7ALTERNATE METHOD FOR CANADIANHIGH-ALTITUDE DERATENATURAL GAS LP GASFIGURE 14MANIFOLD PRESSURE-CHANGE LABELTHE MANIFOLD PRESSURE OF THI

Seite 12 - HORIZONTAL DIRECTION

2Before beginning any troubleshooting procedure, complete the following installation checklist. A furnace malfunction issometimes caused by an imprope

Seite 13 - A0991-01

20TURN OFF ELECTRIC POWER ATTHE FUSE BOX OR SERVICE PANELBEFORE MAKING ANYELECTRICAL CONNECTIONS.ALSO, THE GROUND CONNECTIONMUST BE COMPLETED BEFOREMA

Seite 14 - SPECIAL VENT SYSTEMS (SVS)

21FIELD INSTALLED OPTIONACCESSORIESELECTRONIC AIR CLEANERElectronic air cleaner line voltagepower can be supplied from the screwterminal “EAC” and a l

Seite 15 - POWER VENT SYSTEMS

22I400FIGURE 17UT Electronic Controls 1028-928 CONTROL BOARD, TWINNING CONNECTION -- SINGLE STAGE OPERATIONa099201

Seite 16 - GAS SUPPLY AND PIPING

23FIGURE 18UTEC 1028-928 CONTROL BOARD, TWINNING CONNECTION -- TWO-STAGE OPERATIONa099301

Seite 17 - LP CONVERSION

24LIGHTING INSTRUCTIONSThis appliance is equipped with a directspark ignition device. This device lightsthe main burners each time the roomthermostat

Seite 18 - SETTING GAS PRESSURE

25SETTING BLOWER TIMINGSThe UT Electronic Controls controlboards have four quick connectterminals for connecting the motorspeed leads. These are:1. FA

Seite 19 - Input BTU/HR =

26AIR FLOWThe importance of proper air flow overthe heat exchanger cannot be overemphasized. One of the most commoncauses of heat exchanger failure is

Seite 20 - THERMOSTAT

27BLOWER PERFORMANCE DATA – (-)GPN UPFLOW/HORIZONTAL MODELSBLOWER PERFORMANCE DATA – (-)GPP UPFLOW/HORIZONTAL MODELSMODELNUMBER(-)GPN-SERIESBLOWERSIZE

Seite 21 - INSTALLATIONS

28LIMIT CONTROLThe high limit cut-off temperature is setat the factory and cannot be adjusted.The temperature setting prevents theair temperature leav

Seite 22 - FIGURE 17

29FIGURE 23FILTER RETAINING RODDISCONNECT MAIN ELECTRICALPOWER TO THE UNIT BEFOREATTEMPTING ANY MAINTENANCE.FAILURE TO DO SO CAN CAUSEELECTRICAL SHOCK

Seite 23 - FIGURE 18

33IMPORTANT: TO INSURE PROPER INSTALLATION AND OPERATION OFTHIS PRODUCT, COMPLETELY READ ALL INSTRUCTIONS PRIOR TOATTEMPTING TO ASSEMBLE, INSTALL, OPE

Seite 24 - START-UP PROCEDURE

FIGURE 25FILTER RETAINING ROD (SIDE RETURN)30FILTERROD45-24095-01FILTER RODSUPPORTANGLEAE-60520-01FILTER SUPPORTANGLE(SEE ANGLE DETAIL)AE-61883-01FILT

Seite 25 - CHANGING BLOWER SPEED

31IMPORTANT: Do not operate thesystem without filters. A portion of thedust entrained in the air may temporarilylodge in the air duct runs and at thes

Seite 26 - AIR FLOW

32FIGURE 26TROUBLESHOOTING FLOWCHARTGO TOEWARNINGINTEGRATED FURNACE CONTROL (IFC)TROUBLESHOOTING GUIDEHAZARDOUS VOLTAGELINE VOLTAGECONNECTIONSDISCONNE

Seite 27

33FIGURE 27FOR MODELS WITH UT ELECTRONIC CONTROLS 1028-928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION

Seite 28 - SAFETY FEATURES

34FIGURE 28FOR MODELS WITH UT ELECTRONIC CONTROLS 1027-200 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION

Seite 31 - Advise The Customer To:

4USE ONLY WITH TYPE OF GASAPPROVED FOR THIS FURNACE.REFER TO THE FURNACE RATINGPLATE.INSTALL THIS FURNACE ONLY INA LOCATION AND POSITION ASSPECIFIED I

Seite 32 - TROUBLESHOOTING GUIDE

5GENERAL INFORMATIONDO NOT USE THIS FURNACEDURING CONSTRUCTION IF AIRLADEN CORROSIVE COMPOUNDSARE PRESENT SUCH AS CHLORINEAND FLUORINE. OTHERWISE,PROV

Seite 33 - FIGURE 27

6CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)UPFLOW/HORIZONTAL MODELSTOPLEFT SIDEFRONTRIGHT SIDEBOTTOMRETURNAIRSUPPLYAIR2613/16265/82411/322411/3219/329

Seite 34 - FIGURE 28

7CLEARANCE –ACCESSIBILITYThe design of forced air furnaces withinput ratings as listed in the tables onthe following pages are certified byCSA for the

Seite 35

8FAILURE TO PREVENT PRODUCTSOF COMBUSTION FROM BEINGCIRCULATED INTO THE LIVINGSPACE CAN CREATE POTENTIALLYHAZARDOUS CONDITIONS,INCLUDING CARBON MONOXI

Seite 36 - 36 CM 0604

9THIS FURNACE AND ANY OTHERFUEL-BURNING APPLIANCE MUSTBE PROVIDED WITH ENOUGHFRESH AIR FOR PROPERCOMBUSTION AND VENTILATIONOF THE FLUE GASES. MOSTHOME