System Alert Mode – Standby System Faults
System Alert Display Fault Cause Fault Remedy
Switch G Coil Fail 1. Transfer switch generator coil failure. 1. Contact authorized service center.
Switch U Coil Fail 1. Transfer switch utility coil failure. 1. Contact authorized service center.
Generator Start Switch in OFF Position 1. Generator start switch in OFF
position.
1. Set generator switch to AUTO
position.
2. StatStation display too far away from
transmitter.
2. Locate display within 200 ft (60 m) of
transmitter.
3. Transmitter located in an area that
interferes with the transmitter RF
signal.
3. Locate transmitter in a location free
of RF interference.
4. Transmitter, generator, or transfer
switch signal wiring fault.
4. Contact authorized service center.
Fuse Fail 1. 2 Amp fuse in transfer switch failed. 1. Check/replace fuse.
2. Wiring failure. 2. Contact authorized service center.
One Wire Communication Fail 1. Signal wire failure between generator,
transfer switch, and transmitter.
1. Contact authorized service center.
Transmitter Battery Low 1. Transmitter batteries low. 1. Replace transmitter batteries.
StatStation System Fault
System Sync Unsuccessful 1. Batteries exhausted.
2. Display console too far from
transmitter or other signal
interference.
1. Replace with fresh AA batteries.
2. Move console closer to transmitter.
Replace transmitter AA batteries.