General Construction
Part B Specification and Response Requirements
Annexure 2- Minimum Design & Construction Specification
Page 74 Updated 19/07/2013
Provide for double headed pillar hydrant(s) in a location(s) that complies with the
requirements detailed in AS2419.1 or as detailed on the drawings. . The hydrant standpipe
shall be 100mm NB galvanised “Heavy” steel pipe to AS1074, wrapped against corrosion
below ground level using “Denso” tape. Outlets shall be SA Metropolitan Fire Service type
64mm bronze globe valves with male hose fitting and cap. Valve outlets are to face in the
horizontal plane at a height of between 1000mm and 1200mm above finished ground level.
Paint the standpipe white, valves and caps Fire Brigade red with 2 coats of enamel paint
over etching primer.
The hydrant system will be required to provide a minimum flow as required under the current
Building Regulations. The Builder shall be responsible for making arrangements and testing
of the complete fire service to standards as required by the SA Metropolitan Fire Service and
SA Water.
3.16.7 Site stormwater drainage
Front and rear yard spaces shall be graded so that they are effectively drained to ensure that
site stormwater does not pond on the site or flow to and from adjacent properties as per the
design drawings.
Unless otherwise specified all sumps shall be a Grated Inlet in accordance with the attached
detail and in garden areas shall be installed in concrete a minimum of 100 mm thick and
600 mm in diameter or 600 mm square.
SAHT strongly discourages the use of pumps in stormwater disposal systems and unless
otherwise detailed they are not to be used.
Unless otherwise detailed pipework shall be a minimum of 90 mm uPVC stormwater grade
and under common drives 100 mm sewer class uPVC.
All grates in single units shall be class medium traffic and in single units class light traffic.
Where driveways back fall towards the unit provide a grated channel capable of carrying light
vehicular traffic.
At Practical Completion provide an Engineer’s certificate that the installed system complies
with the approved design
3.16.8 Stormwater Retention/Detention
3.16.8.1 General
An on site above ground Stormwater Retention system plumbed into the WC cistern is
required on all houses as detailed on SAHT Drawing SK 01 (Rev B) included in “Standard
Details” in Book B.
3.16.8.2 Tanks
The tanks shall be 1000 litre round or rectangular “Colobond” or pre-finished colour rainwater
tank permanently fixed on a suitable structural galvanised steel stand and concrete footing
system designed for the site conditions.