General Construction
Part B Specification and Response Requirements
Annexure 2- Minimum Design & Construction Specification
Page 64 Updated 19/07/2013
3.13. TILING
3.13.1 Water-proofing
All waterproofing shall meet the requirements set out in the “Ministers Specification SA F1.7”,
the BCA and AS 3740.
In addition to those requirements the whole of the bathroom floor is to be waterproofed.
The whole of the bathroom floor (including the shower alcove) is to be waterproofed and
returned up the walls as a cove to 150mm min. above the finished floor level. At the door
way the waterproofing is to extend to the top of the brass edge angle.
Use an approved manufacturers system such as BEAUMONTS ‘BARRIERFLEX’, ABA
‘SUPERFLEX 3’ or CROMMELIN CHEMICALS WETITE or equal approved.
Other wet area wall, floor and fixture junctions shall be in accordance with the SA wet area
details as detailed in the BCA and Minister’s Specification..
3.13.2 Falls
In addition to the requirements of the South Australian Housing Code, the following falls shall
be achieved on the finished floor surface:-
Shower area between 1:50 and 1:60
Other wet areas between 1:80 and 1:100
3.13.3 Colour scheme
Colour coordinate floor and wall tiles with accessories and paint colours.
The colour of the grout for the floor tiling shall be medium grey or colour matched to the tiles.
White grout is not to be used for floor tiling.
Provide matching feature frieze or pattern tiles to all wet area walls.
3.13.4 Tiles
The following tiles are to be used.