General Construction
Part B Specification and Response Requirements
Annexure 2- Minimum Design & Construction Specification
Page 87 Updated 19/07/2013
An exhaust fan shall be provided over the hot plates, but located in line with the front of the
cooker, ducted to outside air including closing mechanisms when not in use;
3.17.13.2 Cooker Models
The following cookers will be supplied and installed by OTHERS:-
Gas cookers are to be Electrolux Chef upright cooker model number GBC5266 W
upright type set into recess in cupboards/bench tops in accordance with
manufacturer’s recommendations
Electric cookers are to be Electrolux Chef upright model number EBC 5271 W
upright type set into recess in cupboard/bench tops in accordance with
manufacturer’s recommendations.
3.17.13.3 Gas Termination.
The Proponent is responsible for supplying and testing the gas service. The connection to
the cooker (by others) will be a hose connection to allow the cooker to be shifted out for
maintenance and cleaning. The supply is to terminate behind the cooker at a height of
approximately 800 mm above floor level and approximately 150 mm from the right hand side
of the cooker opening.
The Galvanized steel spigot coming through the wall shall be securely fixed to the studwork (
a trimmer may be required) and shall have a 90 degree elbow pointing down to the floor,
capped with a screw on cap. The elbow shall be located close to the wall but with sufficient
gap to allow the installer to attach a hose connection. The pipe work is not to protrude more
than 40 mm from the wall finish.
3.17.13.4 Electrical Termination
The Proponent is responsible for supplying and testing the electrical service including an
isolator located as required by AS 3000. The connection to the cooker (by others) will be via
a length of cable to enable the cooker to be easily removed for maintenance or cleaning.
The supply is to terminate behind the cooker at a height of approximately 800 mm above
floor level and approximately 150 mm from the right hand side of the cooker opening.
Terminate the cable into a Clipsal Cooker Socket (31VCS) or equal approved. Supply a
Clipsal Cooker Plug (800CL) or equal approved and leave in the cupboard adjacent to the
cooker for the cooker installer to connect. Where an alternative product is proposed the
socket and plug shall be compatible.
3.17.14 Telephone
Provide one telephone point with a double GPO nearby to the kitchen over bench top away
from sink and another point in Bedroom 1.
Telephone points shall have face plates and be pre-wired underground in a capped conduit
to the Telstra service point at the boundary, all to the current Telstra requirements.
Check the prewiring to ensure that the cable is free of obstructions.
The external Telstra service point should be mounted on the side wall of the house adjacent
the electrical meter box with clearance from the meter box to suit Telstra requirements.
The Telephone cables may utilize the conduits supplied for future NBN installations but are
to be provided unless NBN install their cables and equipment at the time of construction.